AVK BS 750 Type 1 UNDERGROUND HYDRANT
Various Outlets available, PN16
Mamoun Humayra
Water Product Manager
Fire hydrant BS750 Type 1 suitable for use with water and neutral liquids.
The Series 29/61 is a Type 1, end of line, fire hydrant complying to all relevant standards. Suitable for use with water and neutral liquids, to a maximum temperature of 70°C. Complies with requirements of BS 750 and BS EN1074-2:2004 and EN 14339:2005, underground hydrants. Also to BS EN 1074-6 for potable (drinking) water.
Variant 29/61-002 | |
---|---|
Connection: | Flanged |
Material: | Ductile Iron |
DN: | DN80 - DN80 |
PN: | PN 16 |
Closing direction: | Clockwise to Close |
Features
- Fully maintainable
- Ductile iron construction
- 2½” London round thread outlet to BS 750
- Exceeds flow requirements: - Kv = 92 minimum 2000l/min - Kv = 113 actual 2470l/min
- Corrosion resistant construction, compliant with BS EN 1074-6 for disinfection products
- Inlet flange drilled BS EN 1092:1997, PN10/16
- Inlet is of a proprietary type
- Draining stopper
- Low weight design
- Blue fusion bonded epoxy coating
- Options:
- Outlet options: - Stainless steel or Gunmetal to BS 750 round thread - Instantaneous (Morris) - Belfast - London “V” thread - Internal screwed Norwegian - Bayonet (Dublin)
- Note:
- It is recommended that applications in a corrosive atmosphere or sited in exposed locations use a stainless steel stem 1.4404 (316) and all exposed fasteners in A4 stainless steel.
Downloads
Datasheet
Appendix
Certificate(s)
Flyer
Price list
Reference nos. and dimensions:
Scroll for more info
Ref. no. | DN mm |
H3 mm |
H11 mm |
L mm |
W5 mm |
W mm |
Theoretical weight/kg |
Notes |
---|---|---|---|---|---|---|---|---|
29-080-61-21413100 | 80 | 447 | 235 | 318 | 150 | 200 | 21 | Gunmetal |
29-080-61-21414100 | 80 | 447 | 235 | 318 | 150 | 200 | 21 | 2.5RT Stainless Steel |
29-080-61-21417100 | 80 | 447 | 235 | 318 | 150 | 200 | 21 | Belfast outlet |
Enquiry
Scroll for more info
Test/Approvals
- Approved according to WRAS
- Drinking Water Inspectorate Regulation 31 compliant
- Made in Great Britain
Standards
- Designed according to BS750:2006, Designed according to BS EN 1074 -1 and 2, Designed according to EN 14339:2005
- Standard flange drilling to EN1092 (ISO 7005-2), PN 16